Patton electronic Network Card 1004 User Manual

USER  
MANUAL  
MODEL 1004  
and 1004S  
High Speed,  
Multipoint Short  
Range Modem  
Part# 07M1004-C  
Doc# 047011UC  
Revised 8/10/95  
SALES OFFICE  
(301) 975-1000  
TECHNICAL SUPPORT  
(301) 975-1007  
 
3.0 CONFIGURATION  
The Model 1004 is configured using six PC board mounted switch-  
es. Figure 1 shows the switch locations, along with the location of the  
terminal blocks and optional surge protectors:  
3.2 ACCESSING THE CONFIGURATION SWITCHES  
The five switches shown in Figure 3 configure the Model 1004 for  
RTS/CTS delay, echo, method of carrier control, impedance and  
2-wire/4-wire operation. These switches are located internally on the  
Model 1004's PC board. To access switch set 1 (SW1) and switch set  
2 (SW2), use a small flat blade screwdriver to pop open the Model  
1004's case as shown in Figure 4.  
DCE/DTE  
Switch  
Surge  
Suppressors  
(1004S only)  
2-Wire/4-Wire  
Switch  
“ON”  
Terminal  
Block  
Control  
Switches  
“OFF”  
1
2
3
4
SW1  
SW2  
Figure 1. Model 1004 board, showing switch locations  
Figure 3. Close up of switches SW1 and SW2 on the PC board  
3.1 SETTING THE DCE/DTE SWITCH  
For your convenience, the Model 1004 has an externally accessi-  
ble DCE/DTE switch (Figure 2). If the device connected to the Model  
1004 is a modem or multiplexer (or is wired like one), set the switch to  
“DTE”. This setting causes the Model 1004 to behave like Data  
Terminal Equipment and transmit data on pin 2.  
If the device connected to the Model 1004 is a PC, terminal or  
host computer (or is wired like one), set the switch to “DCE”. This set-  
ting causes the Model 1004 to behave like Data Communications  
Equipment and transmit data on pin 3.  
DCE  
DTE  
Figure 2. Close up of the external DCE/DTE switch  
Figure 4. Opening the Model 1004's plastic case with a small screwdriver  
3
4
 
3.2.1 SWITCH SETTINGS  
SW 1-4: Impedance  
All possible settings for the Model 1004’s configuration switches  
are presented in the summary table below. If you have additional  
questions, contact Technical Support at (301) 975-1000.  
Switch SW1-4 defines a termination resistance. The Model 1004’s  
generator can drive 50 unit loads including two termination resistances  
of 120 Ohms each.  
SWITCH SUMMARY TABLE  
SW1-4  
Off  
On  
Setting  
High (120K Ohm)  
Low (120 Ohm)  
Position  
SW1-1  
SW1-2  
SW1-3  
SW1-4  
SW2  
Function  
RTS/CTS Delay  
Echo Enable  
Carrier Control  
Impedance  
Off Position  
0mS  
On Position  
8mS  
Echo “Off”  
Echo “On”  
Constantly “On”  
High (120K Ohm)  
2-wire  
Controlled by RTS  
Low (120 Ohm)  
4-wire  
SW 2: 2-Wire/4-Wire  
Switch SW1-4 determines whether the Model 1004 will operate in  
either 2-wire or 4-wire mode.  
2 wire/4 wire  
SW 1-1: RTS/CTS Delay  
SW1-4  
Off  
On  
Setting  
2-wire  
4-wire  
The setting for Switch SW1-1 determines the amount of delay  
between the time the Model 1004 “sees” RTS and when it sends CTS.  
(This option is available in DCE mode only).  
3.2.2 CONFIGURATION SWITCH APPLICATIONS  
SW1-1  
Off  
On  
Setting  
0mS  
8mS  
The table below shows you how to set the Model 1004's configu-  
ration switches to fit several common applications. If you have any  
questions, call Patton Technical Support at (301) 975-1007.  
TYPICAL SWITCH APPLICATIONS  
SW 1-2: Echo Enable  
Point-to-Point  
4W HDX  
Multi-point  
2W  
Switch  
Settings  
Switch SW1-2 determines whether the Model 1004 echoes data  
back to the transmitting device. (Half duplex modes only).  
4W  
2W  
4W  
SW1-2  
Off  
On  
Setting  
Echo Off  
Echo On  
SW1-1: RTS/CTS*  
SW1-2: Echo  
ON  
OFF  
OFF  
ON  
ON  
ON  
ON  
OFF  
ON  
ON  
ON  
ON  
OFF  
ON  
SW1-3: Carrier  
Master-OFF  
Slaves-ON  
SW 1-3: Carrier Control Method  
SW1-4: Impedance  
SW2: 2-wire/4-wire  
ON  
ON  
ON  
ON  
ON  
Master - ON  
Slaves - HIGH  
Last Slave - ON  
Switch SW1-3 determines whether the carrier is “constantly on” or  
“controlled by RTS”. This setting allows for operation in switched carri-  
er, multipoint and/or hardware handshaking applications.  
OFF  
ON  
OFF  
SW1-3  
Off  
On  
Setting  
Constantly “on”  
Controlled by RTS  
*NOTE: RTS/CTS Delay setting should be based upon transmission timing.  
5
6
 
4.0 INSTALLATION  
3. Strip the insulation on each of the twisted pair wires about .25”.  
Once the Model 1004 is properly configured, it is ready to connect  
to your system. This section tells you how to properly connect the  
Model 1004 to the twisted pair and RS-232 interfaces, and how to  
operate the Model 1004.  
4.1 TWISTED PAIR CONNECTION  
4. In a two pair circuit, connect one pair of wires to XMT+ and  
XMT- (transmit positive and negative) on the terminal block, making  
careful note of which color is positive and which color is negative.  
The Model 1004 supports data-only communication between two  
RS-232 devices at distances to 9.4 miles and data rates to 115.2 Kbps.  
There are two essential requirements for installing the Model 1004:  
1. These units work in pairs. Therefore, you must have one Model  
1004 at each end of a two twisted pair interface. In multipoint  
environments, there must be one Model 1004 at the RS-232 host  
and one at each RS-232 terminal.  
5. Connect the other pair of wires to RCV+ and RCV- (receive  
positive and negative) on the terminal block, again making careful note  
of which color is positive and which color is negative.  
2. To function properly, the Model 1004 needs two twisted pairs of  
metallic wire. These pairs must be unconditioned dry metallic  
wire, between 19 and 26 AWG (the higher number gauges may  
limit distance). Standard dial-up telephone circuits, or leased cir-  
cuits that run through signal equalization equipment, are not  
acceptable.  
Ultimately, you will want to construct a two pair crossover cable that  
makes a connection with the two Model 1004s as shown below.  
XMT+--------------------------------------------------RCV+  
One Pair  
}
XMT- --------------------------------------------------RCV-  
G ----------------------To Shield (Optional)  
G
For your convenience, the Model 1004 is available with several  
different twisted pair interfaces: RJ-11 jack, RJ-45 jack, terminal  
blocks with strain relief and dual modular jacks (for multipoint daisy-  
chaining).  
RCV+--------------------------------------------------XMT+  
RCV- --------------------------------------------------XMT-  
One Pair  
}
4.1.1 TWISTED PAIR CONNECTION USING TERMINAL BLOCKS  
6. In a single pair circuit, use only the transmit (XMT) pair as  
If your application requires you to connect one or two pairs of bare  
wires to the Model 1004, you will need to open the case to access the  
terminal blocks. The following instructions will tell you how to open the  
case, connect the bare wires to the terminal blocks and fasten the  
strain relief collar in place so the wires won't pull loose.  
XMT+--------------------------------------------------XMT+  
XMT- --------------------------------------------------XMT-  
shown below:  
1. You should already have the case open for the configuration  
procedure. If not, see Section 3.2.  
7. If there is a shield around the telephone cable, it may be con-  
nected to “G” on the terminal block. To avoid ground loops, we recom-  
mend connecting the shield at the computer end only. A ground wire is  
not necessary for proper operation of the Model 1004.  
2. Strip the outer insulation from the twisted pair(s) about one  
inch from the end.  
7
8
 
8. When you finish connecting the wires to the terminal block, the  
assembly should resemble the diagram below:  
10. Insert the strain relief assembly and wire into the slot in the  
bottom half of the modem case. Set it into the recess in the case.  
9. Place the 2 halves of the strain relief assembly on either side  
of the telephone wire and press together very lightly. Slide the assem-  
bly so that it is about 2 inches from the terminal posts and press  
together firmly. If your cable diameter is too small or too large for our  
strain relief, please contact our technical support. We have strain relief  
assemblies to accommodate most cable diameters.  
11. BEND the top half of the case as necessary to place it over  
the strain relief assembly. Do not snap the case together yet.  
12. Insert one captive screw through a saddle washer. Then  
insert the entire piece through the hole in the DB-25 end of the case.  
Snap that side of the case closed. Repeat the process for the other  
side. This completes cable installation.  
9
10  
 
4.1.2 TWISTED PAIR CONNECTION USING RJ-11 OR RJ-45  
RJ-45 Cable (4-Wire)  
The RJ-11 and RJ-45 connectors on the Model 1004’s twisted pair  
interface are pre-wired for a standard TELCO wiring environment. The  
signal/pin relationships are shown below:  
SIGNAL  
PIN#  
PIN#  
SIGNAL  
GND†  
RCV-  
XMT+  
XMT-  
RCV+  
GND†  
2-----------------------7  
3-----------------------5  
4-----------------------6  
5-----------------------3  
6-----------------------4  
7-----------------------2  
GND†  
XMT-  
RCV+  
RCV-  
XMT+  
GND†  
RJ-11  
SIGNAL  
RJ-45  
SIGNAL  
1...................GND†  
2...................RCV-  
3...................XMT+  
4...................XMT-  
5...................RCV+  
6...................GND  
1...................N/C  
2...................GND  
3...................RCV-  
4...................XMT+  
5...................XMT-  
6...................RCV+  
7...................GND  
8...................N/C  
RJ-11 Cable (2-Wire)  
SIGNAL  
PIN#  
PIN#  
SIGNAL  
Connection to ground is optional  
XMT+  
XMT-  
3-----------------------3  
4-----------------------4  
XMT+  
XMT-  
1
2
3
4
5
6
7
8
1
2
3
4
5
6
RJ-45 Cable (2-Wire)  
SIGNAL  
PIN#  
PIN#  
SIGNAL  
XMT+  
XMT-  
4-----------------------4  
5-----------------------5  
XMT+  
XMT-  
AT&T standard modular color codes  
When connecting two Model 1004’s, it is necessary to use a  
crossover cable. The diagrams below show how a crossover cable  
should be constructed for the following environments: 4-wire RJ-11,  
4-wire RJ-45, 2-wire RJ-11 or 2-wire RJ-45.  
Connection to ground is optional  
4.2 WIRING FOR MULTIPOINT CIRCUITS  
RJ-11 Cable (4-Wire)  
The Model 1004 supports multi-point applications using either a  
star or daisy chain topology. Both topologies require special wiring, as  
well as specific DIP switch settings for master and slave units. Note:  
Refer to Section 3.2.2 for multipoint DIP switch settings.  
SIGNAL  
PIN#  
PIN#  
SIGNAL  
GND†  
RCV-  
XMT+  
XMT-  
RCV+  
GND†  
1-----------------------6  
2-----------------------4  
3-----------------------5  
4-----------------------2  
5-----------------------3  
6-----------------------1  
GND†  
XMT-  
RCV+  
RCV-  
XMT+  
GND†  
4.2.1 STAR TOPOLOGY  
Using a star topology, you may connect several Model 1004s  
together in a master/slave arrangement. Maximum distance between  
the units will vary based upon the number of drops, data rate, wire  
gauge, etc. Call Technical Support for specific distance estimates.  
Connection to ground is optional  
11  
12  
 
Figure 4 shows how to wire the two-pair cables properly for a  
Model 1004 star topology. Note that the ground connection is not  
needed.  
With the dual modular units, you won't need to build cumbersome  
“Y” cables for your daisy chain application. Simply use a crossover  
cable to go between the host and the first slave (see Section 4.1.2 for  
crossover cable wiring instructions), and straight through cables  
between the slaves.  
HOST  
FIRST SLAVE  
SECOND SLAVE  
XMT+  
RCV+  
4.3 CONNECTION TO THE RS-232 INTERFACE  
RCV+  
Once you have properly configured the Model 1004 and connect-  
ed the twisted pair wires correctly, simply plug the Model 1004 directly  
into the DB-25 port of the RS-232 device. Remember to insert and  
tighten the two captive connector screws.  
XMT-  
RCV+  
RCV-  
RCV-  
XMT+  
XMT-  
RCV-  
XMT+  
XMT-  
(Note: If you must use a cable to connect the Model 1004 to the  
RS-232 device, make sure it is a straight through cable of the shortest  
possible length—we recommend 6 feet or less).  
Figure 4. Star wiring for Model 1004 host and slaves  
4.4 OPERATING THE MODEL 1004  
Once the Model 1004 is properly installed, it should operate trans-  
parently—as if it were a standard cable connection. Operating power  
is derived from the RS-232 data and control signals; there is no  
“ON/OFF” switch. All data signals from the RS-232 and RS-485 inter-  
faces are passed straight through. Additionally, one hardware flow  
control signal is passed in each direction.  
4.2.2 DAISY CHAIN TOPOLOGY  
Using a daisy chain topology, you may connect several Model  
1004s together in a master/slave arrangement. Maximum distance  
between the units will vary based upon the number of drops, data rate,  
wire gauge, etc. Call Technical Support for specific distance estimates.  
Figure 5 shows how to wire the two-pair cables properly for a  
Model 1004 daisy chain topology. Note that the ground connection is  
not needed.  
HOST  
FIRST SLAVE  
OTHER SLAVE(S)  
XMT+---------------------RCV+-----------------------RCV+  
XMT- --------------------RCV- -----------------------RCV-  
RCV+---------------------XMT+-----------------------XMT+  
RCV- --------------------XMT- -----------------------XMT-  
Figure 5. Daisy chain wiring for Model 1004 host and slaves  
Optional Connection: Dual Modular Jacks  
To facilitate daisy chaining, the Model 1004 is available in a  
“DRJ11” (dual RJ-11) or “DRJ45” (dual RJ-45) version. These units  
have two specially wired modular jacks for twisted pair connection.  
13  
14  
 
APPENDIX A  
APPENDIX B  
SPECIFICATIONS  
RS-232 PIN CONFIGURATIONS  
Transmission Format: Asynchronous  
DIRECTION  
“DCE” SETTING  
DIRECTION  
Data Rate: Up to 115,200 bps  
Transmit Line: 2, 4 wire unconditioned twisted pair  
Transmit Mode: Full or half duplex  
Transmit Level: 0 dBm  
1- (FG) Frame Ground  
2- (TD) Transmit Data  
3- (RD) Receive Data  
4- (RTS) Request to Send  
5- (CTS) Clear to Send  
6- (DSR) Data Set Ready  
7- (SG) Signal Ground  
To Model 1004  
From Model 1004  
To Model 1004  
From Model 1004  
From Model 1004  
To Model 1004  
Data Term. Ready (DTR) - 20  
8- (DCD) Data Carrier Detect From Model 1004  
Range: Up to 9 miles  
Control Signals: In DCE mode, DSR turns “ON” immediately after the  
terminal raises DTR; DCD turns “ON” after recogniz  
ing the receive signal from the line; CTS turns on  
after the terminal raises RTS  
Carrier: The carrier is switch selected either continuous operation or  
DIRECTION  
“DTE” SETTING  
DIRECTION  
switched operation, controlled by RTS  
1- (FG) Frame Ground  
Surge Protection: 600W power dissipation at 1 mS and response  
2- (TD) Transmit Data  
From Model 1004  
To Model 1004  
From Model 1004  
To Model 1004  
To Model 1004  
time less than 1.0 pS  
3- (RD) Receive Data  
4- (RTS) Request to Send  
5- (CTS) Clear to Send  
6- (DSR) Data Set Ready  
7- (SG) Signal Ground  
8- (DCD) Data Carrier Detect  
Power: No external power required, uses ultra low power from EIA  
data and control signals  
From Model 1004 Data Term. Ready (DTR) - 20  
To Model 1004  
Size: 2.66” x 2.10” x 0.73”  
15  
16  
 
APPENDIX C  
BLOCK DIAGRAM  
17  
 

MTD Trimmer YM26CO YM26CS YM26SS YM26BC User Manual
Multiquip Drums EM120P User Manual
Multi Tech Systems Network Card MT3334SMI User Manual
NEC Projector LT220 User Manual
Newcon Optik Binoculars BN5 User Manual
NordicTrack Treadmill NTL18940 User Manual
Omega Engineering Marine Instruments CN1001 RTD User Manual
Orion Car Audio Car Speaker HCCA102 User Manual
Panasonic Air Cleaner EH3015 User Manual
Panasonic VCR AJ SD755 User Manual